>> PRODUCTS >> FIREPROOF MASSES AND PASTES >> FLAME CABEL I PASTE >> APPLICATION
1 - flexible wall with a thickness of min. 100 mm
2 - metal pipe, diameter "D" and pipe wall thickness "t"
3 - fireproof paste Flame Cabel I Paste, dimensions: length L = min. 500 mm,
thickness s1 = min. 1.2 mm, paste additionally used for length g1 = min. 5 mm,
inside the partition
4 - the space between the pipe and the partition structure, max. a = 30 mm,
filled with mineral wool with a density of min. 50 kg / m3
5 - gypsum mortar with a thickness of min. g1 = 5 mm
1 - rigid wall with a thickness of min. 100 mm
2 - metal pipe, diameter "D" and pipe wall thickness "t"
3 - fireproof paste Flame Cabel I Paste, dimensions: length L = min. 500 mm,
thickness s1 = min. 1.2 mm, paste additionally used for length g1 = min. 5 mm
inside the partition
4 - the space between the pipe and the partition structure, max. a = 30 mm,
filled with mineral wool with a density of min. 50 kg / m3
5 - gypsum mortar with a thickness of min. g1 = 5 mm
1 - rigid wall with a thickness of min. 150 mm
2 - metal or plastic pipe; diameter "D" and thickness
pipe wall "t"
3 - fireproof paste Flame Cabel I Paste (pipe cover), length L = min. 500 mm
and thickness g1 = min. 1.2 mm
4 - fireproof paste Flame Cabel I Paste (ring on the floor around the sealing)
length e = min. 50 mm and thickness g2 = min. 0.6 mm
5 - the space between the pipe and the partition structure filled with mineral wool with
density min. 50 kg / m3 or cement mortar, width max. u = 30 mm
1 - floor with a minimum thickness of 150 mm;
2 - metal pipe, diameter "D" and pipe wall thickness "t"
3 - fireproof paste Flame Cabel I Paste (pipe cover),
thickness g1 = min. 1.2 mm and min. 500 mm
4 - fireproof paste Flame Cabel I Paste
(ring on the floor around the sealing),
thickness g2 = min. 0.6 mm; length e = min. 60 mm
5 - the space between the pipe and the partition structure filled with mortar
thickness u = max. 15 mm