FOAM ZZ 330
Fire protection foam:
Combo passes
Flammable pipes in insulation
Non-flammable pipes in insulation
Cables and cable trays
Find out more> Buy on the purchasing platform>
>> PRODUCTS >> INTUMESCENT WRAPS >> MULTITUBE >> INSTALLATION
1 - wall thickness B ≥ 150 mm
2 - PE-X pipe, diameter "D" and th. pipe wall "t"
3 - Multitube fireproof tape [hxs] mm, located inside the wall, in
middle of its cross-section
4 - electrically clamped band or adhesive tape
5 - the space between the pipe and the wall, filled with a thickness of cement mortar
u ≤ 25 mm
1 - flexible or rigid wall with a thickness of B = min. 100 mm
2 - bundle of plastic pipes: 4 x PE-X pipe, max. 20 mm and th. walls 2.0 mm
3 - Multitube fireproof tape, dimensions [hxs], centrally located in
the middle of the wall
4 - electrically clamped band or adhesive tape
5 - the gap between the pipe and the partition, width "a", filled with mineral wool
with a density of min. 60 kg / m3
6 - gypsum mortar with a thickness of g1 = min. 5 mm
1 - reinforced concrete floor, thickness B ≥ 150 mm
2 - plastic pipe, diameter "D" and pipe wall thickness "t"
3 - Multitube fireproof tape [hxs] mm, placed inside the floor, at the
distance of 15 ± 5 mm from the bottom of the floor
4 - electrically clamped band or adhesive tape
5 - space between the pipe and the floor, filled with cement mortar with a thickness
u ≤ 25 mm