top of page

 >>  PRODUCTS  >>  INTUMESCENT WRAPS  >>  MULTITUBE  >>  INSTALLATION

1 - rigid wall thickness B = min. 150 mm
2 - plastic pipe, diameter "D" and pipe wall thickness "t"
3 - Multitube fireproof tape (inside), dimensions [hxs], placed
  centrally  inside the wall
4 - electrically clamped band or adhesive tape
5 - the gap between the pipe and the partition with a maximum width of 25 mm,  filled  
  cement mortar or mineral wool with a density of min. 5 0 kg / m3 and closed
  gypsum mortar with a thickness of min. 5 mm

1 - reinforced concrete floor, thickness B = min. 150 mm
2 - plastic pipe, diameter "D" and pipe wall thickness "t"
3 - Multitube fireproof tape (inside) [hxs] mm, placed at the distance
  l = 15 ± 5 mm  from the underside of the floor
4 - electrically clamped band or adhesive tape
5 - the gap between the pipe and the partition, width u = max. 25 mm, filled
  cement mortar

* Detailed information can be found at ETA