top of page

 >>  PRODUCTS  >>  INTUMESCENT WRAPS  >>  MULTITUBE  >>  INSTALLATION

1 - rigid wall thickness B = min. 150 mm
2 - plastic pipe, diameter "D" and pipe wall thickness "t"
3 - Multitube fireproof tape (inside), dimensions [hxs], placed
  centrally  inside the wall
4 - electrically clamped band or adhesive tape
5 - the gap between the pipe and the partition with a maximum width of 25 mm,  filled  
  cement mortar or mineral wool with a density of min. 5 0 kg / m3 and closed
  gypsum mortar with a thickness of min. 5 mm

1 - reinforced concrete floor, thickness B = min. 150 mm
2 - plastic pipe, diameter "D" and pipe wall thickness "t"
3 - Multitube fireproof tape (inside) [hxs] mm, placed at the distance
  l = 15 ± 5 mm  from the underside of the floor
4 - electrically clamped band or adhesive tape
5 - the gap between the pipe and the partition, width u = max. 25 mm, filled
  cement mortar

* Detailed information can be found at ETA

Refer to the Table below for the length of the Multitube fireproof tape for the given pipe diameter. Then measure it out and cut it off with a knife