top of page
FOAM ZZ 330
Fire protection foam:
Combo passes
Flammable pipes in insulation
Non-flammable pipes in insulation
Cables and cable trays
Find out more> Buy on the purchasing platform>
>> PRODUCTS >> FIRE COLLARS >> CARBOCOLLAR CC SMOOTH / SEGMENT >> TECHNICAL INSTALLATION
1 - reinforced concrete floor, thickness B = min. 150 mm
2 - Syncopex CO PN6 / 95 C, CW PN10 / 70C double heating pipe (corrugated PE-HD pipe, diameter D ≤ 110 and pipe wall thickness 0.5 mm),
with inside max. with two PE-X pipes: - at Wed. D1 ≤ 21 mm and th. pipe walls t = 2.5 mm - diam. D1 ≤ 17 mm and th. pipe walls t = 2.5 mm
3, 4 - two layers of PE insulation, total thickness 32 mm (2 x 16 mm), continuous insulation
5 - the space between the insulation of the inner pipe and the corrugated pipe
6 - corrugated PE-HD pipe, diameter D ≤ 110 and pipe wall thickness 0.5 mm
8 - CarboCollar CC fireproof collar, located at the bottom of the floor
7 - fireproof collar fastening - expansion anchor bolts
The space between the floor and the pipe, filled with cement mortar, thick. u = max. 25 mm
* Detailed information can be found at ETA
METHOD OF SEALING A DOUBLE HEATING PIPE SYNCOPEX CO PN6 / 95 C, CW PN10 / 70C WITH PE INSULATION (COMPACT PIPES)
PENETRATING FLOOR ACCORDING TO ETA-16/0189*
bottom of page