CarboCollar CC Fireproof Collar - Technical Installation 8 | Carboline Polska
top of page

        >>  PRODUCTS  >>  FIRE COLLARS  >>  CARBOCOLLAR CC SMOOTH / SEGMENT  >>  TECHNICAL INSTALLATION

1 - rigid floor with a thickness of B = min. 150 mm
2 - plastic pipe, diameter "D" and wall thickness "t"
3 - CarboCollar CC fireproof collar mounted at the bottom of the floor
4 - fireproof collar fastening - expansion anchor bolts M6x60 or M8x80
5 - A1 type cables according to EN 1366-3, max. 10 cables
6 - the space between the pipe and the wall structure, filled with cement mortar, o  thickness of u = max. 10 mm

* Detailed information can be found at ETA

METHOD OF SEALING A PLASTIC PIPE WITH CABLES TYPE A1 INSIDE PENETRATING FLOOR ACCORDING TO ETA-16/0189*

bottom of page