1 - rigid wall thickness B = min. 100 mm
2 - plastic pipe, diameter "D" and wall thickness "t"
3 - the space between the pipe insulation and the wall structure in width  u = max. 15 mm,  
   filled with gypsum plaster to the depth  min. 10 mm
4 - CarboCollar CC fireproof collar on the outside of the wall, mounted on both
     sides of the wall
5 - fixing the fireproof collar - expansion anchor bolts M6x60 or M8x80

* Detailed information can be found at ETA

Fill the space between the pipe insulation and the aperture tightly. Use cement mortar
Place fireproof collar on the pipe insulation. In case of fireproof collars with a diameter of CC-125 and larger with a segmented cover  S, first wrap the pipe four times with an intumescent insert and then put the steel cover it

Pull the locking pin of the clamping buckle through the fixing slot on the other end of the fireproof collar and fold it 180 ° backwards so that the collar is firmly closed on the pipe insulation

Attach the fireproof collar to the wall using expansion anchor bolts

Mark the completed penetration seal with the label attached to the set. Mark CarboCollar fireproof collar on the label, enter the date and the name

METHOD OF SEALING METAL AND PLASTIC PIPE IN FEF INSULATION PENETRATING A RIGID WALL ACCORDING TO ETA-16/0189*

INSTALLATION OF CARBOCOLLAR CC FIREPROOF COLLAR ON METAL AND PLASTIC PIPE WITH FEF FOAM (RUBBER) INSULATION  PENETRATING A RIGID WALL