FJ203
FIRE ROPE
-
European Technical Approval: ETA-19/0282
-
European Declaration of Performance: FJ203 – 20190807
-
Certificate of Constancy of Performance: 1404-CPR-3174
-
Fire resistance class: up to EI 240
-
Reaction to fire: see ETA19/0282 – A1 class according to 13501-1
-
Color: gray (rock wool)
-
Environment clas: Y1, Y2, Z1, Z2
-
Storage temperature range: from -10°C to +70°C
-
Shelf life: no limit
-
Packaging: FJ203 Ø12mm - 50 m roll, FJ203 Ø20mm - 50 m roll, FJ203 Ø30mm - 50 m roll , FJ203 Ø40mm - 50 m roll, FJ203 Ø50mm - 25 m roll, FJ203 Ø60mm – 25 m roll, FJ203 Ø70mm – 20 m roll, FJ203 Ø80mm – 10 m roll, FJ203 Ø90mm – 10 m roll, FJ203 Ø100mm – 10 m roll, FJ203 Ø120mm – 2 m roll
Examples of technical application
Examples of technical installation of the product:
Select the appropriate fire rope diameter for the given expansion joint width from the table. Place fire rope in the expansion joint and press it with a blunt tool, e.g. a wooden slat
Place fire rope centrally inside the wall, press it with a blunt tool, e.g. a wooden slat
Properly sealed expansion joint with one fire rope in the wall. Fire rope should be inside the wall. The surface of the rope should not protrude beyond the edges of the wall
Place fire ropes on both sides of the wall, inside the expansion joint, press them with a blunt tool, e.g. a wooden slat
Properly sealed expansion joint with two fire ropes in the wall. Fire ropes should be inside the wall. The surface of fire ropes should not protrude beyond the edges of the wall
Select the appropriate fire rope diameter for the given expansion joint width from the table. Place fire rope in the expansion joint and press it with a blunt tool, e.g. a wooden slat
Properly sealed expansion joint with one fire rope in the floor. Fire rope should be inside the floor. The surface of the rope should not protrude beyond the edges of the floor
Select the appropriate fire rope diameter for the given expansion joint width from the table. Place fire ropes on both sides of expansion joint, press them with a blunt tool, e.g. a wooden slat
Properly sealed expansion joint with two fire ropes in the floor. Fire ropes should be inside the floor. The surface of fire ropes should not protrude beyond the edges of the floor
Technical description:
Technical description
FJ203 fire rope is a fireproof woven rope made of mineral rock fiber in a sheath of elastic glass fibers braided appropriately to maintain the shape ensuring optimal filling of expansion joints. Thanks to its design, it ensures easy and quick assembly in all conditions on the construction site.
Intended use:
Intended use
FJ203 fire rope provides fire protection for expansion joints and gaps in concrete fire barriers, walls and floors. By filling the expansion joint, they are a perfect seal for fire partitions in places where there are gaps or expansion joints. All FJ203 fire ropes have been tested in accordance with EN 1366-4:
- expansion joints (+ 20%): joint width from 10 mm to 130 mm (depending on the selected product)
- static joints: joint width from 10 mm to 150 mm (depending on the selected product)
Application:
Application
Joint width 5 mm - 10 mm Required rope diameter – 12 mm
Joint width 11 mm - 15 mm Required rope diameter – 20mm
Joint width 16 mm - 20 mm Required rope diameter – 30 mm
Joint width 21 mm - 30 mm Required rope diameter – 40 mm
Joint width 31 mm - 40 mm Required rope diameter – 50 mm
Joint width 41 mm - 50 mm Required rope diameter – 60 mm
Joint width 51 mm - 60 mm Required rope diameter – 70 mm
Joint width 61 mm - 70 mm Required rope diameter – 80 mm
Joint width 71 mm - 80 mm Required rope diameter – 90 mm
Joint width 81 mm - 90 mm Required rope diameter – 100 mm
Joint width 91 mm - 100 mm Required rope diameter – 120 mm