top of page

 >>  PRODUCTS  >>  FIREPROOF MASSES AND PASTES  >>  FLAME CABEL I PASTE  >>  APPLICATION

1 - a rigid wall with a minimum thickness of 150 mm
2 - plastic pipe, diameter "D" and pipe wall thickness "t"
3 - mineral wool with a density of 50 kg / m3 and a thickness of w = min. 15 mm
4 - fireproof paste Flame Cabel I Paste, min. 4 mm
5 - the space between the mineral wool and the partition structure  
   filled with cement mortar, max. 17.5 mm

1 - floor with a minimum thickness of 150 mm
2 - plastic pipe, diameter "D" and pipe wall thickness "t"
3 - mineral wool, density 50 kg / m3, width max. w = 15 mm
4 - fireproof paste Flame Cabel Paste I, min. 5 mm
5 - the space between the mineral wool and the partition structure  
   filled with cement mortar, max. 17.5 mm

* Detailed information can be found at ETA

Fill the space between the pipe and the partition with mineral wool with a minimum density of 50 kg / m3, leaving 5 mm space from the front of the partition