top of page
FOAM ZZ 330
Fire protection foam:
Combo passes
Flammable pipes in insulation
Non-flammable pipes in insulation
Cables and cable trays
Find out more> Buy on the purchasing platform>
>> PRODUCTS >> FIREPROOF MASSES AND PASTES >> FLAME CABEL I PASTE >> APPLICATION
1 - a rigid wall with a minimum thickness of 150 mm
2 - plastic pipe, diameter "D" and pipe wall thickness "t"
3 - mineral wool with a density of 50 kg / m3 and a thickness of w = min. 15 mm
4 - fireproof paste Flame Cabel I Paste, min. 4 mm
5 - the space between the mineral wool and the partition structure
filled with cement mortar, max. 17.5 mm
1 - floor with a minimum thickness of 150 mm
2 - plastic pipe, diameter "D" and pipe wall thickness "t"
3 - mineral wool, density 50 kg / m3, width max. w = 15 mm
4 - fireproof paste Flame Cabel Paste I, min. 5 mm
5 - the space between the mineral wool and the partition structure
filled with cement mortar, max. 17.5 mm
* Detailed information can be found at ETA
Fill the space between the pipe and the partition with mineral wool with a minimum density of 50 kg / m3, leaving 5 mm space from the front of the partition
Apply Flame Cabel I Paste on the wool with a spatula and create a ring around the pipe, for wall thickness of min. 4 mm, for floor min. 5 mm and a width of min. 15 mm
Sealing should be made on both sides of the partition, both in wall and in floor
Mark the penetration with the attached label, mark fireproof paste Flame Cabel I Paste, enter the date and name
The same solution can be applied on various types of plastic pipes stabilized with glass, aluminum or without stabilization
METHOD OF SEALING PLASTIC PIPES WITH A SMALL DIAMETER PENETRATING WALL OR FLOOR ACCORDING TO ETA-16/0732*
APPLICATION OF FLAME CABEL I PASTE ON PLASTIC PIPES WITH DIAMETER UP TO 40 MM PENETRATING WALL OR FLOOR
THE SCOPE OF APPLICATION OF FLAME CABEL I PASTE DEPENDING ON MATERIAL AND DIAMETER OF PIPE AND TYPE OF PARTITION
bottom of page