Flame Cabel I Paste Fireproof Paste - Application 2 | Carboline Polska
top of page
logo_eu.9ac04f85.png
LSSE-logo-main.png

 >>  PRODUCTS  >>  FIREPROOF MASSES AND PASTES  >>  FLAME CABEL I PASTE  >>  APPLICATION

1 - metal pipe with a diameter D ≤ 273 mm and a pipe wall thickness t from 6.0 to 14.2 mm
2 - fireproof paste Flame Cabel I Paste, length L ≥ 500 mm,

   with a thickness of g2 ≥ 1.2 mm
3 - fireproof paste Flame Cabel I Paste, length s1 ≥ 50 mm,

   with a thickness of g1 ≥ 0.6 mm
4 - the space between the pipe insulation and the penetration seal

   fireproof
paste Flame Cabel I Paste; thickness u ≤ 5 mm
5 - construction details of mixed penetration
6 - rigid floor with a density of min. 1700 kg / m3 and thickness B ≥ 150 mm

* Detailed information can be found at ETA

Fill the aperture in the floor on both sides with mineral wool boards with a minimum density of 150 kg / m3 and a minimum thickness of 50 mm

Using a spatula, apply 1.2 mm thick fireproof paste Flame Cabel A Pasta on the wool.

Using a brush, apply Flame Cabel Pasta I on the partition in such a way that a ring with a width of at least 50 mm and a thickness of at least 0.6 mm is created. Apply Flame Cabel I Paste on the pipe along the length of min. 500 mm and a thickness of min. 1.2 mm

The sealing of the mineral wool filling the partition and the pipes should be done on both sides of the partition, both in wall and in floor

Mark the penetration with the attached label, mark the fireproof paste Flame Cabel I Paste, Flame Cabel A Paste on it, enter the date and name

METHOD OF SEALING METAL PIPE PENETRATING THROUGH FLOOR ACCORDING TO ETA-16/0732*

APPLICATION OF FLAME CABEL I PASTE ON METAL PIPES WITHOUT INSULATION PENETRATING FLOOR

THE SCOPE OF APPLICATION OF FLAME CABEL I PASTE DEPENDING ON MATERIAL AND DIAMETER OF PIPE AND TYPE OF PARTITION