1 - metal pipe with a diameter D ≤ 273 mm and a pipe wall thickness t from 6.0 to 14.2 mm
2 - fireproof paste Flame Cabel I Paste, length L ≥ 500 mm,

   with a thickness of g2 ≥ 1.2 mm
3 - fireproof paste Flame Cabel I Paste, length s1 ≥ 50 mm,

   with a thickness of g1 ≥ 0.6 mm
4 - the space between the pipe insulation and the penetration seal

   fireproof
paste Flame Cabel I Paste; thickness u ≤ 5 mm
5 - construction details of mixed penetration
6 - rigid floor with a density of min. 1700 kg / m3 and thickness B ≥ 150 mm

* Detailed information can be found at ETA

Fill the aperture in the floor on both sides with mineral wool boards with a minimum density of 150 kg / m3 and a minimum thickness of 50 mm

Using a spatula, apply 1.2 mm thick fireproof paste Flame Cabel A Pasta on the wool.

Using a brush, apply Flame Cabel Pasta I on the partition in such a way that a ring with a width of at least 50 mm and a thickness of at least 0.6 mm is created. Apply Flame Cabel I Paste on the pipe along the length of min. 500 mm and a thickness of min. 1.2 mm