top of page

FOAM ZZ 330
Fire protection foam:
Combo passes
Flammable pipes in insulation
Non-flammable pipes in insulation
Cables and cable trays
Find out more> Buy on the purchasing platform>
>> PRODUCTS >> INTUMESCENT WRAPS >> MULTITUBE >> INSTALLATION
1 - rigid wall thickness B = min. 150 mm
2 - plastic pipe, diameter "D" and pipe wall thickness "t"
3 - continuous insulation made of flexible elastomeric foam (FEF), thick
"G", nominal density 45 - 70 kg / m3 and reaction to fire class BL-s2,
d0 according to EN 13501-1
4 - the gap between the pipe insulation and the partition with a maximum width of u = 25 mm,
filled with mineral wool with a density of min. 60 kg / m3 i closed with mortar
gypsum with a thickness of min. 5 mm or filled cement mortar
5 - gypsum mortar with a thickness of g1 = 5 mm
6 - Multitube fireproof intumescent tape (inside), dimensions [hxs],
placed centrally inside the wall
7 - electrically clamped band or adhesive tape
1 - reinforced concrete floor with a thickness of B = min. 150 mm
2 - metal pipe, diameter "D" and pipe wall thickness "t"
3 - continuous insulation made of flexible elastomeric foam (FEF), thick
"G", nominal density 45 - 70 kg / m3 and reaction to fire class BL-s2,
d0 according to EN 13501-1
4 - Multitube fireproof intumescent tape (inside) [hxs] mm; placed at a distance
l = 15 ± 5 mm from the underside of the floor
5 - electrically clamped band or adhesive tape
6 - the gap between the pipe insulation and the partition with the maximum width
u = 25 mm, filled with cement mortar
* Detailed information can be found at ETA
INSTALLATION OF MULTITUBE FIREPROOF INTUMESCENT TAPE ON A METAL PIPE WITH FEF FOAM INSULATION PENETRATING WALL OR FLOOR
Read from the Table below for steel pipes, for copper pipes or for cast iron pipes, the length of the Multitube fireproof tape for the given pipe diameter, measure it and cut it off
with a knife
Wrap the cut piece of fireproof tape around the pipe insulation. Adhere strictly to the number of coils given in Table 11.1 for steel pipes, 11.2 for copper pipes or 11.3 for cast iron pipes.
Secure the tape with an electrically clamped band and slide it into the partition. Location of the tape inside the opening - central position along the wall axis or 10-15 mm from the bottom of the floor
Fill the space between the pipe and the partition with cement mortar
Mark the completed penetration seal with the attached label, mark the Multitube fireproof tape on it, enter the date and
name
TABLE FOR SELECTING THE LENGTH AND NUMBER OF WRAPS OF MULTITUBE FIREPROOF TAPE FOR STEEL PIPES WITH ELASTOMERIC FEF FOAM INSULATION
TABLE FOR SELECTING THE LENGTH AND NUMBER OF WRAPS OF MULTITUBE FIREPROOF TAPE FOR COPPER PIPES WITH ELASTOMERIC FEF FOAM INSULATION
TABLE FOR SELECTING THE LENGTH AND NUMBER OF WRAPS OF MULTITUBE FIREPROOF TAPE FOR CAST IRON PIPES WITH ELASTOMERIC FEF FOAM INSULATION
METHOD OF SEALING A METAL PIPE WITH ELASTOMERIC FEF FOAM INSULATION PENETRATING WALL AND FLOOR ACCORDING TO ETA-15/0511*
bottom of page