1 - reinforced concrete ceiling with a thickness of B = min. 150 mm
2 - plastic pipe, diameter "D" and pipe wall thickness "t"
3 - mineral wool with a density of min. 50 kg / m3 (continuous insulation)
4 - Flame Cabel A Paste on both sides of the floor; length a1 = min.
50 mm, thickness g1 = min. 0.6 mm, width a2 = min. 50 mm,
thickness g2 = min. 0.6 mm
5 - Multitube fireproof intumescent tape [hxs] mm, placed inside the floor, at
the distance of 15 ± 5 mm from the underside of the floor
6 - the space between the floor and the penetration, filled
cement mortar, approx. 25 mm