top of page

 >>  PRODUCTS  >>  INTUMESCENT WRAPS  >>  MULTITUBE  >>  INSTALLATION

1 - rigid wall thickness B = min. 100 mm
2 - plastic pipe, diameter "D" and pipe wall thickness "t"
3 - continuous insulation made of flexible elastomeric foam (FEF), thick
  "G", density

    nominal 45 - 70 kg / m3 and class of reaction to fire  BL- s2, d0 according to EN 13501-1
4 - the gap between the pipe insulation and the partition with a maximum
  width a = 30 mm,

    filled with mineral wool with a density of min.  60 kg / m3
5 - gypsum mortar with a thickness of g1 = min. 5 mm
6 - Multitube fireproof tape (inside), dimensions [hxs],

    placed  centrally  inside the wall
7 - electrically clamped band or adhesive tape

1 - reinforced concrete floor with a thickness of B = min. 150 mm

2 - plastic pipe, diameter "D" and pipe wall thickness "t"

3 - insulation made of flexible elastomeric foam (FEF) with a thickness of "g" 

    (continuous insulation)

4 - Multitube fireproof tape [hxs] mm, placed inside the floor,

    at the  distance  15 ± 5 mm from the underside of the floor

5 - electrically clamped band or adhesive tape

6 - the space between the floor and the penetration, filled  mortar

    cement, approx. 25 mm

* Detailed information can be found at ETA

Read from the table below, the length of the Multitube fireproof intumescent tape for a given pipe diameter, measure it and cut it with a knife

Wrap the cut piece of fireproof tape around the pipe insulation. Strictly stick to the number of wraps given in table below