 >>  PRODUCTS  >>  INTUMESCENT WRAPS  >>  MULTITUBE  >>  INSTALLATION

1 - rigid wall thickness B = min. 150 mm
2 - cable bundle, diameter ≤ 100 mm, consisting of cables with a diameter

  no more than 14 mm
3 - Multitube fireproof tape (inside) [hxs], centrally located in

    the middle of the wall
4 - the gap between the cable bundle and the partition with the maximum width

  u = 25 mm, filled with cement mortar
5 - electrically clamped band or adhesive tape

1 - reinforced concrete floor with a thickness of B = min. 150 mm
2 - cable bundle, diameter ≤ 100 mm, consisting of cables with a diameter

  no more than 14 mm
3 - Multitube fireproof tape (inside) [hxs]; placed at a distance

    l = 15 ± 5 mm  from the underside of the floor
4 - the gap between the cable bundle and the partition, with the maximum width
u = 25 mm, filled with cement mortar
5 - electrically clamped band or adhesive tape

* Detailed information can be found at ETA