1 - wall thickness B ≥ 200 mm
2 - cables, cable bundles with or without pipes (max.hole filling up to 60%)  
  surface area)
3 - pre-insulated metal pipes
4 - plastic pipes with or without cables
5 - ZZ 330 Foam

* Detailed information can be found at ETA

Place the pipe with the cables in the hole.  

NOTE: the diameter of the mounting hole should be min. 130% of the pipe diameter
Fill the space between partition and pipe with ZZ 330 Foam
Cut off any excess ZZ 330 foam residue with a knife. You can use it to build the next penetration
The space between the pipe and the partition must be completely sealed
Mark the completed penetration with the attached label, mark ZZ 330 Foam on it, enter the date and name
Place the pipes in hole
Fill the empty space between partition and pipes with ZZ 330 Foam
Cut off any excess ZZ 330 foam residue with a knife. You can use it to build the next penetration
The space between the pipe bundle and the partition must be completely sealed
Mark the completed penetration with the attached label, mark ZZ 330 Foam on it, enter the date and name
Place the cables in the hole.  

NOTE: the diameter of the mounting hole should be min. 130% of the beam diameter
Fill the empty space between the partition and the cables with ZZ 330 Foam
Cut off any excess ZZ 330 foam residue with a knife. You can use it to build the next penetration
The space between the cables and the partition must be completely sealed
Mark the completed penetration with the attached label, mark ZZ 330 Foam on it, enter the date and name

METHOD OF SEALING CABLES, CABLE BUNDLES, PRE-INSULATED METAL PIPES, PLASTIC PIPES WITH CABLES OR WITHOUT PENETRATING WALL AND FLOOR ACCORDING TO ETA-10/0431*

APPLICATION OF ZZ 330 FOAM ON FLAMMABLE PIPES WITH CABLES INSIDE PENETRATING WALL OR FLOOR

APPLICATION OF ZZ 330 FOAM ON METAL PIPES IN PE FOAM INSULATION PENETRATING WALL OR FLOOR

APPLICATION OF ZZ 330 FOAM ON CABLE BUNDLES PENETRATING WALL OR FLOOR