        >>  PRODUCTS  >>  FIRE COLLARS  >>  CARBOCOLLAR CC SMOOTH / SEGMENT  >>  TECHNICAL INSTALLATION

1 - rigid floor with a thickness of min. 150 mm 
2 - plastic or metal pipe, diameter "D" i  wall thickness "t"
3 - continuous insulation made of flexible elastomeric foam (FEF), thickness "g", 
     density nominal 45 ÷ 70 kg / m3 and reaction to fire class BL-s2,  d0 according to
     EN 13501-1

4 - CarboCollar CC fireproof collar, mounted at the bottom of the floor
5 - fireproof collar fastening - expansion anchor bolts M6x60 or M8x80
6 - the space between the pipe and the wall structure, filled with mortar  cement, with
     thickness u = max. 10 mm

* Detailed information can be found at ETA