1 - rigid floor with a thickness of B = min. 150 mm
2 - plastic pipe, diameter "D" and wall thickness "t"
3 - CarboCollar CC fireproof collar, mounted at the bottom of the floor
4 - fixing the fireproof collar - expansion anchor bolts M6x60 or M8x80
5 - the space between the pipe and the wall structure, filled with mortar cement,
with a thickness of u = max. 10 mm
METHOD OF SEALING A PLASTIC PIPE WITHOUT INSULATION PENETRATING FLOOR ACCORDING TO ETA-16/0189*
* Detailed information can be found at ETA
Fill the space between the pipe wall and the aperture tightly. Use cement mortar
Place fireproof collar on the pipe. In case of collars with a diameter of CC-125 and larger with a segmented cover S, first wrap the pipe four times with an intumescent insert and then put the steel cover on top
Pull the locking pin of the clamping buckle through the fixing slot on the other end of the collar and fold it 180 ° backwards so that the collar is firmly closed on the pipe
Attach the fireproof collar to the floor using expansion anchor bolts
Mark the completed penetration seal with the label attached to the set. Mark CarboCollar fireproof collar on the label, enter the date and the name
CARBOCOLLAR CC FIREPROOF COLLAR SELECTION CHART FOR THE MOST COMMON PLASTIC PIPES
INSTALLATION OF CARBOCOLLAR CC FIREPROOF COLLAR ON A PLASTIC PIPE PENETRATING THE FLOOR