>> PRODUCTS >> FIRE COLLARS >> CARBOCOLLAR CC SMOOTH / SEGMENT >> TECHNICAL INSTALLATION
METHOD OF SEALING A PLASTIC PIPE WITHOUT INSULATION PENETRATING A WALL ACCORDING TO ETA-16/0189*
1 - rigid wall thickness B = min. 100 mm
2 - plastic pipe, diameter "D" and wall thickness "t"
3 - the space between the pipe insulation and the wall structure in width
u = max. 15 mm,
filled with gypsum plaster to a depth of min. 10 mm
4 - CarboCollar CC fireproof collar on the outside of the wall, mounted on
both sides of the wall
1 - flexible wall, thickness B = min. 125 mm
2 - plastic pipe, diameter "D" and th. walls "t"; space between
pipe insulation and the wall structure with a width of u = max. 15 mm
3 - CarboCollar CC fireproof collar on the outside of the wall, mounted on the
both sides of the wall
4 - fixing fireproof collar - expansion anchor bolts M6x60 or M8x80
* Detailed information can be found at ETA
Fill the space between the pipe wall and the aperture tightly. Use cement mortar
Place the fire collar on pipe. In case of collars with a diameter of CC-125 and larger with a segmented cover S, first wrap the pipe four times with an intumescent insert and then put the steel cover on it
Pull the securing pin of the clamping buckle through the securing slot on the other end of the fireproof collar and fold it 180 ° backwards so that the collar locks firmly on the pipe
Attach the fireproof collar to the wall with expansion anchor bolts.
Mark the completed penetration seal with the label attached to the set. Mark CarboCollar fireproof collar on the label, enter the date and the name
Fill the space between the pipe wall and the aperture tightly. Use cement mortar
Place the fire collar on pipe. In case of collars with a diameter of CC-125 and larger with a segmented cover S, first wrap the pipe four times with an intumescent insert and then put the steel cover on it
Pull the securing pin of the clamping buckle through the securing slot on the other end of the fireproof collar and fold it 180 ° backwards so that the collar locks firmly on the pipe
Attach the fireproof collar to the wall with expansion anchor bolts.
Mark the completed penetration seal with the label attached to the set. Mark CarboCollar fireproof collar on the label, enter the date and the name
INSTALLATION OF CARBOCOLLAR CC FIREPROOF COLLAR ON A PLASTIC PIPE PENETRATING A RIGID AND FLEXIBLE WALL