top of page

 >>  PRODUCTS  >>  FIREPROOF COLLARS  >>  CARBOCOLLAR CC SLIM

SLIM

FIREPROOF COLLAR

PRODUCT OFFICIAL DOCUMENTS

PRODUCT TECHNICAL DATA

OTHER DOCUMENTS FOR DOWNLOAD

  • Technical data sheet

  • MSDS

  • Certification Mark

  • European Technical Approval: ETA-16/0189, (25/09/2023)

  • Certificate of Constancy of Performance: 1488-CPR-0579/W

  • European Declaration of Performance: DoP CC-009-1-2023-06-02

  • Fire resistance class: up to EI 180 C/U, U/C

  • Reaction to fire: B-s2, d0

  • Color: silver

  • Environment class:  Z2

  • Storage temperature range: from + 5°C to + 30°C

  • Shelf life: no limit, no longer than 24 months

  • Packaging: 1 piece

Examples of technical installation of the product:

ADDITIONAL PRODUCTS THAT CAN BE USED WITH CARBOCOLLAR CC FIREPROOF COLLARS:

synthetic, flexible elastomeric foam (FEF) according to EN 14304, fire reaction class BL-s3, d0, according to EN 13501-1 and density 45 ÷ 70 kg / m3,
 
Insulating Tubolit PE foam , with reaction to fire class E according to EN 13501-1, and with a nominal density of 30 kg / m3,
 
PE acoustic mat (Weberfloor 4955 db mat), reaction to fire class Bfl-s1 according to EN 13501-1, and with a nominal mass per unit area of 12 kg / 30 m2. The PE acoustic mat is recommended in floors, especially when it is required to reduce the acoustic effects of sewage pipes -  additional sound absorption of the mat up to 19 dB with one wrapping.

Technical description:

CarboCollar CC SLIM fireproof collar is a metal cylindrical flexible clamping ring mounted on a pipe. It consists of an outer cover made of a single or multi-segment stainless steel sheet and one or more inserts made of intumescent material, which in case of fire increases its volume and closes the opening. The steel cover is equipped with a clamp, used to fasten the fireproof collar and stabilize it on the pipe, and with mounting brackets with holes through which expansion anchor bolts are led, fixing fireproof collar to the partition. The fireproof collar is delivered as a ready-made product.

Intended use:

CarboCollar CC SLIM is a product intended for fireproof sealing of service penetrations and mixed penetrations in walls and floors of plastic pipes without insulation or with FEF or PE foam insulation, metal pipes insulated with FEF or PE foam, electric cables. The possible fire resistance class ranges from EI 30 to EI 180. With the use of CarboCollar CC SLIM fireproof collars, it is possible to seal single pipes or pipe bundles, pipes in groups of e.g. 4 pieces, cable bundles, pipe bends that are mounted just below the floor. Other information can be found in the ETA. Good fire-retardant properties make the CarboCollar CC SLIM fireproof collars suitable for sealing pipes with particularly large diameters and where large thicknesses of flammable insulation on steel pipes are required. The product is intended for professional use.

Installation:

BETON bez cieniapng.png
FLOOR

Floors made of concrete or reinforced concrete, with a thickness of not less than 150 mm and a density of not less than 1700 kg / m3

width from 150 mm



REINFORCED CONCRETE
CEGŁA bez cienia.png
RIGID WALL

Walls made of concrete, reinforced concrete, cellular concrete, solid brick, hollow or checkered brick, with a thickness of not less than 100 or 125 mm and a density of not less than 600 kg / m3

width from 100 mm or 125 mm

AIR CONCRETE, CONCRETE, BRICK, OTHER CERAMIC PRODUCTS
Piktogram Ytong.png
RIGID WALL

Walls made of concrete, reinforced concrete, cellular concrete, solid brick, hollow or checkered brick, with a thickness of not less than 100 or 125 mm and a density of not less than 600 kg / m3

width from 100 mm or 125 mm

AIR CONCRETE, CONCRETE, BRICK, OTHER CERAMIC PRODUCTS
Regips bez cienia.png
FLEXIBLE WALL

Walls not less than 125 mm thick, with a skeleton structure made of steel or wooden sections

width from 125 mm



PLASTERBOARD

Installation information:

Fireproof collar is delivered ready for installation or as an assembly set. The inner diameter of the fireproof collar should be fitted to the outer diameter of the protected installation element (pipe, insulation, cable). Two fireproof collars are required for walls.  In case of floors, install one fireproof collar on both sides of the partition on the lower side of the floor. For proper installation and use, adjusting the cover or the intumescent insert to the pipe diameter, always follow the instructions in the CC-IM1 / CC-IM2 manual. which are attached to the product. The CarboCollar CC fireproof collar should be attached to the wall or floors with the use of symmetrically placed expansion anchor bolts (M6x60 mm or M8x80 mm).

30 MM CARBOCOLLAR FIREPROOF COLLARS - MINIMUM NUMBER OF EXPANSION ANCHOR BOLTS

Technical description
Przeznaczenie
Installation
Installation information
Examples of technical installation
bottom of page