Flame Cabel A Paste Painted Board - Application 1 | Carboline Polska
top of page
logo_eu.9ac04f85.png
LSSE-logo-main.png

 >>  PRODUCTS  >>  FIREPROOF MASSES AND PASTES  >>  FLAME CABEL A PASTE PAINTED BOARD  >>  INSTALLATION

1 - rigid wall with a density of min. 600 kg / m3 and thickness B ≥ 150 mm or floor    

    with a density of min. 1700 kg / m3 and thickness B ≥ 150 mm
2 - 2 mineral wool boards with a density of min. 150 kg / m3, with a thickness of a ≥ 50 

     mm, covered with fireproof paste Flame Cabel A Pasta  with a thickness of t1 ≥ 1.2

     mm; b ≥ 50 mm (space  between the boards)

3 - fireproof paste Flame Cabel A Paste, length ≥ 50 mm and thickness ≤ 5.0 mm
4 - fireproof paste Flame Cabel A Paste on both sides of the wall or floor

    (located on perimeter of the penetration), length d ≥ 60 mm

    and thickness t2 ≥ 0.6 mm

Cut the correct shape with a knife to fit Flame Cabel A Paste Painted Board for pipes or cable bundles

The fragments of Flame Cabel A Paste Painted Board cut this way place in the partition so that the painted layer of Flame Cabel A Paste is together with the partition surface

Use the Flame Cabel A Paste in the cartridge to seal the gaps between the arranged fragments of Flame Cabel A Paste Painted Board and the places where the board and partition meet

Sealing of the mixed penetration should be made on both sides of the partition both in wall and in floor
Seal pipes and cables in accordance with the instructions in the information leaflet or product catalog
Mark the penetration with the attached certificate, mark fireproof paste Flame Cabel A Paste on it, enter the date and name

INSTALLATION OF FLAME CABEL A PASTE PAINTED BOARD IN EXPANSION JOINTS

Use a knife to cut a strip of Flame Cabel A Paste Painted Board with a width equal to the width of the expansion joint

Previously cut off strip
place in
expansion joint so that the top layer of
Flame Cabel A Paste is together with
partition surface

If the partition is thicker than 100 mm, then the space between the applied Flame Cabel A Paste Painted Board strips should be filled with any mineral wool
If the protection must be made on both sides, place the strip of Flame Cabel A Paste Painted Board in the expansion joint on the opposite side of the partition

The gaps between Flame Cabel A Paste Painted Boards should be sealed with Flame Cabel A Paste in cartridge

View of a properly sealed expansion joint on one and both sides. In this way, you can seal horizontal and vertical joints both in walls and floors

CONSTRUCTION DETAILS OF MIXED PENETRATION ACCORDING TO ETA-16/0732

INSTALLATION OF ​FLAME CABEL A PASTE PAINTED BOARD IN MIXED PENETRATIONS

bottom of page