1 - rigid floor with a thickness of B ≥ 150 mm and density ≥ 1700 kg / m3
2 - mineral wool with a density of not less than 80 kg / m3
 
3 - fireproof paste Flame Cabel A Paste placed on the top of expansion joint
with the thickness
 t1 ≥ 1.6 mm
4 - rigid wall, thickness B ≥ 150 mm and density ≥ 600 kg / m3
 

The symbol indicates the side of the partition exposed to fire

1 - rigid floor with a thickness of B ≥ 150 mm and density ≥ 1700 kg / m3
2 - mineral wool with a density of not less than 80 kg / m3
 
3 - fireproof paste Flame Cabel A Paste placed at the bottom of the
expansion
 joint with the thickness t1 ≥ 1.6 mm
4 - rigid wall, thickness B ≥ 150 mm and density ≥ 600 kg / m3

 
The symbol indicates the side of the partition exposed to fire

* Detailed information can be found at ETA

In case of floor: the gap should be tightly filled with mineral wool with a minimum density of 80 kg / m3 (the thickness of the wool should be equal to the thickness of the floor)