Flame Cabel A Paste Fireproof Paste - Application 8 | Carboline Polska
top of page

 >>  PRODUCTS  >>  FIREPROOF MASSES AND PASTES  >>  FLAME CABEL A PASTE  >>  APPLICATION

1 - rigid floor with a thickness of B ≥ 150 mm and density ≥ 1700 kg / m3
2 - mineral wool with a density of not less than 80 kg / m3
 
3 - fireproof paste Flame Cabel A Paste placed on the top of expansion joint
with the thickness
 t1 ≥ 1.6 mm
4 - rigid wall, thickness B ≥ 150 mm and density ≥ 600 kg / m3
 

The symbol indicates the side of the partition exposed to fire

1 - rigid floor with a thickness of B ≥ 150 mm and density ≥ 1700 kg / m3
2 - mineral wool with a density of not less than 80 kg / m3
 
3 - fireproof paste Flame Cabel A Paste placed at the bottom of the
expansion
 joint with the thickness t1 ≥ 1.6 mm
4 - rigid wall, thickness B ≥ 150 mm and density ≥ 600 kg / m3

 
The symbol indicates the side of the partition exposed to fire

* Detailed information can be found at ETA

In case of floor: the gap should be tightly filled with mineral wool with a minimum density of 80 kg / m3 (the thickness of the wool should be equal to the thickness of the floor)

On the mineral wool boards placed in the gap, apply the Flame Cabel A Paste fireproof paste from the bottom or top of the floor with a spatula (layer thickness is given in the technical drawing above)

The view of the properly applied fireproof paste Flame Cabel A Paste

The view of a properly sealed expansion joint in floor

APPLICATION OF FIREPROOF PASTE FLAME CABEL A PASTE ON EXPANSION JOINTS IN WALL CLOSE TO FLOOR

In case of joining floor and wall: the gap should be tightly filled with mineral wool with a minimum density of 80 kg / m3 (the thickness of the wool should be equal to the thickness of the wall)

Using a spatula apply fireproof paste Flame Cabel A Paste on one side of mineral wool boards placed in the gap,  (layer thickness is given in the technical drawing above)

The view of the properly applied fireproof paste Flame Cabel A Paste

The view of a properly sealed expansion joint at the joint of wall and floor

METHOD OF SEALING EXPANSION JOINT IN FLOOR OR WALL CLOSE TO FLOOR ACCORDING TO ETA-15/0853*

APPLICATION OF FIREPROOF PASTE FLAME CABEL A PASTE ON EXPANSION JOINTS IN FLOOR

bottom of page