 >>  PRODUCTS  >>  FIREPROOF MASSES AND PASTES  >>  FLAME CABEL A PASTE  >>  APPLICATION

1 - rigid wall with a thickness of B ≥ 150 mm, density ≥ 600 kg / m3 and D = 6.5 ÷ 100 mm 
2 - mineral wool with a density of not less than 80 kg / m3 
6 - fireproof paste Flame Cabel A Paste placed on one side of the expansion joint, with
   the thickness t2 ≥ 1.6 mm

1 - rigid wall with a thickness of B ≥ 150 mm and density ≥ 600 kg / m3 and D = 5 ÷ 65 mm
2 - mineral wool with a density of not less than 80 kg / m3
6 - fireproof paste Flame Cabel A Paste placed on one side of the expansion joint, with

    the thickness t2 ≥ 1.6 mm

* Detailed information can be found at ETA

Fill the gap in the wall with mineral wool boards with a minimum density of 120 kg / m3
and a thickness equal to the width of the partition

Using a spatula, apply a 1.6 mm thick layer of Flame Cabel A Pasta on the wool.

A layer of fireproof paste Flame Cabel A Paste should be applied only on one side of the partition

The view of a properly sealed expansion joint

METHOD OF SEALING EXPANSION JOINT IN WALL ACCORDING TO ETA-15/0853*

APPLICATION OF FIREPROOF PASTE FLAME CABEL A PASTE ON EXPANSION JOINTS IN WALL