 >>  PRODUCTS  >>  FIREPROOF MASSES AND PASTES  >>  FLAME CABEL A PASTE  >>  APPLICATION

1 - rigid wall with a thickness of B ≥ 150 mm, density ≥ 600 kg / m3 and D = 5 ÷ 60 mm 
2 - mineral wool with a density of not less than 120 kg / m3 
6 - fireproof paste Flame Cabel A Paste, thickness t2 ≥ 2.5 mm, t3 ≥ 3 mm

* Detailed information can be found at ETA

Apply Flame Cabel A Paste on both sides (the layer thickness is given in the technical drawing above) of mineral wool board with a minimum density of 80 kg / m3 (board thickness should be half of the expansion joint depth) by using a spatula
Place the prepared mineral wool boards inside the expansion joint at one of its edges
On the inside of the gap, apply fireproof paste Flame Cabel A Paste on the inside of the mineral wool boards with a spatula (thickness of the layer is given in the technical drawing above)
Fill the remaining gap with 80 kg / m3 mineral wool boards with previously applied Flame Cabel Paste A, the same as in step 1
The view of a properly sealed expansion joint

METHOD OF SEALIG EXPANSION JOINT IN WALL ACCORDING TO ETA-15/0853*

APPLICATION OF FLAME CABEL A PASTE ON EXPANSION JOINTS IN WALL