1 - flexible or rigid wall with a thickness of min. 100 mm
2 - metal pipe, diameter "D" and pipe wall thickness "t"
3 - mineral wool with a density of min. 80 kg / m3 and thickness g = 30 mm
  (continuous insulation)
4 - the space between the pipe and the partition structure, max.
    a = 30 mm, filled with mineral wool with a density of min. 50 kg / m3
5 - gypsum mortar with a thickness of min. g1 = 5 mm
6 - fireproof paste Flame Cabel A Paste, dimensions: b = min. 50 mm and h = min.
  0.6 mm  (on the pipe insulation); c = min. 50 mm and h1 = min. 0.6 mm (ring on
  wall around the penetration seal)

1 - rigid wall with a thickness of min. 100 mm
2 - metal pipe, diameter "D" and pipe wall thickness "t"
3 - mineral wool with a density of min. 80 kg / m3 and thickness g = 30 mm
   (continuous insulation)
4 - the space between the pipe and the partition structure, max. a =
   30 mm, filled with mineral wool with a density of min. 50 kg / m3
5 - gypsum mortar with a thickness of min. g1 = 5 mm
6 - fireproof paste Flame Cabel A Paste, dimensions: b = min. 50 mm and h =
   min. 0.6  mm (on the pipe insulation); c = min. 50 mm and h1 = min. 0.6 mm (ring on
   wall around the penetration seal)

* Detailed information can be found at ETA

Fill the space between the pipe insulation and the partition tightly. Use mineral wool with a density of min. 60 kg / m3

Using a spatula, apply Flame Cabel A Paste on the partition in such a way that a ring with a width of min. 50 mm and a thickness of min. 0.6 mm is created

Apply Flame Cabel A Paste on the pipe cover to form a ring with a width of min. 50 mm and a thickness of min. 0.6 mm

Sealing should be done on both sides of the partition
Mark the penetration seal with the attached label, mark Flame Cabel Pasta A on it, enter the date and name

TABLE OF SEAL SELECTION DEPENDING ON PIPE MATERIAL AND ITS DIMENSIONS

METHOD OF PROTECTING METAL PIPE IN THE INSULATION OF MINERAL WOOL PENETRATING WALL ACCORDING TO ETA-16/0732*

APPLICATION OF FLAME CABEL A PASTE ON PIPE INSULATED WITH MINERAL WOOL PENETRATING WALL