>>  PRODUCTS  >>  INTUMESCENT WRAPS  >>  CARBOWRAP CW  >>  INSTALLATION

1 - a rigid wall with a thickness of B ≥ 100 or 150 mm (see Annex B)
2 - plastic pipe, diameter "D" and pipe wall thickness
  "T" (see Annexes B and D)
3 - CarboWrap CW fireproof wrap, dimensions [hxs], placed in
  in the middle  the cross-section of the wall
4 - space between the pipe and the wall structure, width u = max.
  30 mm, filled with cement mortar or mineral wool with g density
  min. 50 kg / m3

1 - rigid floor with a thickness of B ≥ 150 mm
2 - plastic pipe, diameter "D" and pipe wall thickness "t"
  (see Annexes B and D)
3 - CarboWrap CW fireproof wrap, dimensions [hxs] mm; placed at the
  distance l = 10 mm from the underside of the floor
4 - space between the pipe and the floor structure, width u = max.
  25 mm, filled with cement mortar

* Detailed information can be found at ETA