>>  PRODUCTS  >>  INTUMESCENT WRAPS  >>  CARBOWRAP CW  >>  INSTALLATION

1 - a rigid wall with a thickness of B ≥ 100 or 150 mm (see Annex B)
2 - plastic pipe, diameter "D" and pipe wall thickness
  "T" (see Annexes B and D)
3 - CarboWrap CW fireproof wrap, dimensions [hxs], placed in
  in the middle  the cross-section of the wall
4 - space between the pipe and the wall structure, width u = max.
  30 mm, filled with cement mortar or mineral wool with g density
  min. 50 kg / m3

1 - rigid floor with a thickness of B ≥ 150 mm
2 - plastic pipe, diameter "D" and pipe wall thickness "t"
  (see Annexes B and D)
3 - CarboWrap CW fireproof wrap, dimensions [hxs] mm; placed at the
  distance l = 10 mm from the underside of the floor
4 - space between the pipe and the floor structure, width u = max.
  25 mm, filled with cement mortar

* Detailed information can be found at ETA

Read from the Pipe Diameter Chart below and select the appropriate size of the CarboWrap CW Fireproof wrap
Wrap CarboWrap CW around the pipe and secure it with the integrated adhesive