 >>  PRODUCTS  >>  FIREPROOF MASSES AND PASTES  >>  FLAME CABEL COATING  >>  APPLICATION

1 - floor with a minimum thickness of 150 mm
2 - cable tray
3 - cables with a diameter of max. 21 mm
4 -
fireproof
 Flame Cabel Coating; on both sides of the floor,
  length L = min. 300 mm, depth k = min. 30 mm,
  thickness g2 = min. 1.2 mm
5 - Flame Cabel Coating, on both sides of the floor,

   dimensions: f = min. 50 mm, e = min. 50 mm, g1 = min. 0.6 mm
6 - mineral wool, density 50 kg / m3, thickness w = max. 40 mm

1 - flexible or rigid wall with a thickness of min. 125 mm
2 - cable tray
3 - cables with a diameter of max. 21 mm
4 -
fireproof 
Flame Cabel Coating; on both sides of the partition,
  of length L = min. 300 mm, depth k = min. 30 mm,
  thickness g2 = min. 1.2 mm
5 -
fireproof
  Flame Cabel Coating, on both sides of partition, dimensions:
  f = min. 50 mm, e = min. 50 mm, g1 = min. 0.6 mm
6 - mineral wool, with a density of min. 50 kg / m3, thickness w = max. 40 mm

1 - flexible or rigid wall with a thickness of min. 100 mm
2 - single cable with a diameter of max. 13 mm
3 -
fireproof
 Flame Cabel Coating dimensions:
  length L = min. 300 mm, thickness h = min. 1.2 mm,
  length l1 = min. 50 mm, thickness h1 = min. 0.6 mm
4 - space between the pipe and the partition structure, max.
 
   a = 30 mm, filled with mineral wool with a density of min. 50 kg / m3
5 - gypsum mortar with a thickness of min. g1 = 5 mm